ADF LINEA 100 NMV DUO Petunjuk Suplemen - Halaman 4
Jelajahi secara online atau unduh pdf Petunjuk Suplemen untuk Perapian Dalam Ruangan ADF LINEA 100 NMV DUO. ADF LINEA 100 NMV DUO 17 halaman. Double sided inbuilt heater zero clearance box
ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
Allowance for side cabinetry (Front elevation):
100mm
100mm
• If the heater is required to be built into cabinetry to either side of the heater,
the minimum clearance to a solid combustible wall is 350mm; as long as no
vents included on that side. See Fig. 3 shown on RHS of heater.
• If Cabinetry is required on both sides of the heater, then the Vents need to
moved to the front of the heater; with equal size and positions equivalent to
the side vents.
• If the vents are included on the sides, the minimum clearance to
combustibles in front of the top vent is 1.2m.
• Note the top vent must be made from a non-combustible heat resistant
material.
350mm
100mm
300mm
1/11/19
Fig. 3
4