ADF LINEA 100 NMV DUO Інструкція з додавання - Сторінка 4

Переглянути онлайн або завантажити pdf Інструкція з додавання для Внутрішній камін ADF LINEA 100 NMV DUO. ADF LINEA 100 NMV DUO 17 сторінок. Double sided inbuilt heater zero clearance box

ADF LINEA 100 NMV DUO Інструкція з додавання
ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
Allowance for side cabinetry (Front elevation):
100mm
100mm
• If the heater is required to be built into cabinetry to either side of the heater,
the minimum clearance to a solid combustible wall is 350mm; as long as no
vents included on that side. See Fig. 3 shown on RHS of heater.
• If Cabinetry is required on both sides of the heater, then the Vents need to
moved to the front of the heater; with equal size and positions equivalent to
the side vents.
• If the vents are included on the sides, the minimum clearance to
combustibles in front of the top vent is 1.2m.
• Note the top vent must be made from a non-combustible heat resistant
material.
350mm
100mm
300mm
1/11/19
Fig. 3
4