Avantco 178GDICE49FB Panduan Servis - Halaman 6

Jelajahi secara online atau unduh pdf Panduan Servis untuk Penata barang dagangan Avantco 178GDICE49FB. Avantco 178GDICE49FB 18 halaman. Ice merchandisers

Avantco 178GDICE49FB Panduan Servis
Temperature Controller Settings
(Continued)
Code
Dripping time after defrost, evaporator fan is off
(Temperature taken from defrost probe)
Maximum time between consecutive defrost cycles
Compressor, fan, and auxiliary start delay when unit is turned
Maximum set point for temperature for when in continuous
Minimum set point for temperature for when in continuous
Temperature differential from set point (Tells compressor when
to turn back on after reaching set temperature)
Set point for when in continuous cycle mode
www.AvantcoRefrigeration.com
6
Service Manual
Ice Merchandisers
Description
Evaporator fan management
Maximum defrost duration/length
Temperature that defrost ends
on
cycle mode
cycle mode
Probe 2 calibration
(Evaporator temperature)
Probe 1 calibration
(Cabinet temperature)
Options
0 = Fan is always running
1 = Fan runs based on difference of cabinet
probe temperature and evaporator probe
temperature
2 = Fan runs based on evaporator probe
temperature
0 to 15 min.
1 - 250 min.
-5° - 200°
0 = Unit will never go into defrost
1-250 = Time in hours
0 - 15 min.
r1 to 200°
-50° - r2
0.1° - 20°
r1 - r2
-20° - 20°
-20° - 20°
Default
2
2 min.
30 min.
58°
3 hours
2 min.
10°
-7.6°
2.0°
18°