Chapter 2
Rack Installation Specifications
2.2
Installable Racks
Figure 2.6 Unit Installation Area
Front door of the rack
Table 2.3 Specifications for the Unit Installation Area
Specification
(1)
Rack front space
(Space between the fixed part of the ETERNUS DX on the
front side and the front of the rack)
(2)
Mount bracket length
(Size between each end of the front and rear rack pillars)
(3)
Rack space
(Space between the fixed part of the ETERNUS DX on the
front side and the rear of the rack)
(4)
Rack mount kit installation area
■
Placement Requirements
When determining service areas, refer to the manual of the rack that is to be used.
Make sure to perform the installation according to the placement requirements described in
Specifications" (page 10)
(1)
(2)
ETERNUS DX
(4)
Rack pillars
and
"1.6 Installation Environment" (page
FUJITSU Storage ETERNUS DX60 S3 Disk storage system Site Planning Guide
Copyright 2015 FUJITSU LIMITED
(3)
Rack rails
Rear door of the rack
Condition
40mm or more
685mm or more
775mm or less
830mm or more
482mm or more
(recommended)
19).
39
"1.1 Installation
P3AM-8982-03ENZ0