Aqua Logic DSHP-4-WCMD Panduan Instalasi dan Pemeliharaan - Halaman 4

Jelajahi secara online atau unduh pdf Panduan Instalasi dan Pemeliharaan untuk Pompa Panas Aqua Logic DSHP-4-WCMD. Aqua Logic DSHP-4-WCMD 9 halaman.

WARNING: DO NOT over tighten water fittings.
Mount Heat Pump on a flat pad and away for water spray.
Give at least 1 ft all the way around unit for servicing.
Install evaporator water inlet and outlet.
Install condenser water inlet and outlet.
Test water fittings for leaks.
Apply electrical power to the Heat Pump.
Adjust the controller to the desired water temperature. (See "Operation and Programming")
Important:
Regulate condenser water until pressure on the pressure gauge reads between 115 to 125 PSIG for models
DSHP-4-WCMD thru DSHP-9-WCMD and 195 to 220 PSIG for model DSHP-10-WCMD. Check after 15 minutes of run
time, adjust the water flow (if needed) to the correct pressure.
Warning: This unit must have proper water flow rate both on the evaporator and
the condenser to operate correctly.
HEAT PUMP SET-UP AJUSTMENTS
Copyright© 2016 Aqua Logic, Inc. Effective date of 1/2016
4