Step 1: Set channel addresses and channel load type
The Sensor has one output channel:
Channel 1 - Switched Output
and one input channel:
Channel 3 - Microwave Sensor
To relate the function of different channels it is necessary
to set the addresses correctly. For example, a scene
select message sent from a device with a Local Code of 1
will only be actioned by devices that also have a Local
Code of 1.
To program the settings for a specific channel on the
Sensor you must specify the appropriate channel number
(i.e.1 to 3) using the programming device.
If no channel number (or channel 0) is specified, all
channels will be set to the same address.
The output channel also has a Circuit number. This allows
different physical channels to be linked and controlled as
a single Circuit.
Basic programming