Allied Telesis AT-8900 SERIES Panduan Pemasangan Cepat - Halaman 8
Jelajahi secara online atau unduh pdf Panduan Pemasangan Cepat untuk Perangkat lunak Allied Telesis AT-8900 SERIES. Allied Telesis AT-8900 SERIES 13 halaman. How to set up pppoe between a linux client and access concentrator
Juga untuk Allied Telesis AT-8900 SERIES: Pemecahan masalah (5 halaman), Bagaimana-Cara (8 halaman)
8
The wall-mount kit is purchased separately. To order a wall-mount kit, contact your
authorised Allied Telesyn distributor or reseller for more information, or visit
http:// www.alliedtelesyn.co.nz/support/at8900.
6.
Apply power to the PSU
For AC Models:
Read the AT-8900 Series Statutory and Safety Information booklet before
connecting a PSU to an AC power source.
Plug the provided AC power cord into the AC power inlet on the rear
panel of the PSU and connect the PSU to the mains power supply.
Important information for service personnel only:
•
CAUTION: double pole/neutral fusing
•
The ratings of fuses FH101 and FH102 is 250 V, 5 A
For DC models:
Read the AT-8900 Series Statutory and Safety Information booklet before
connecting a PSU to a DC power source.
Only trained and qualified personnel should connect a DC power supply.
For centralized DC power connection, the switch should be installed only in
Restricted Access Areas (Dedicated Equipment Rooms, Equipment Closets, or
the like) in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NAPA 70.
DC supply cable specifications:
•
Three core cable is required
•
Minimum core size: 3.3 mm
•
Minimum cable rating: 600 V, 90 degrees Celsius
DC power supply specifications:
•
40 to 60 V, 48 V nominal
•
Supports either positive grounded or negative grounded operation
Circuit protection:
•
10 Amp certified/Listed circuit breaker is required for branch circuit
protection
To connect the DC supply:
Ensure that the supply cable is not live.
1.
Remove the transparent protective terminal cover.
2.
Strip the supply cable wires to expose 7.5mm (0.31 in.) of bare
conductor. Terminate with JST FN5.5-5 or equivalent, using a crimp
tool.
2
(12 AWG) high strand count copper wire
AT-8900 Series
C613-04048-01 REV B