The external motor is connected to the
cooker hood by means of a special
control cable and is operated by the
control elements on the cooker hood.
The electrical system must comply with
local and national safety regulations (BS
7671 in the UK).
For increased safety, it is recommended
to protect the appliance with a suitable
residual current device (RCD) with a trip
current of 30 mA.
The relevant connection data can be
found on the data plate (see "After sales
service and warranty"). Ensure that this
data matches the voltage and
frequency of your household mains
supply.
The external motor is supplied with a
5 m extension cable. If the control
cable needs to be extended further
by means of an additional extension
cable or a hardwired connection
cable (at least 6 x 1.5 mm²), the
installation must conform to local
and national electrical safety
regulations.
Equipotential bonding is required in
this case.
The external motor is supplied with
an earthed connection point .
This external motor has been
designed to be connected to a
suitable Miele cooker hood only.

Electrical connection