Burkert 2103 Series Panduan Memulai Cepat - Halaman 8

Jelajahi secara online atau unduh pdf Panduan Memulai Cepat untuk Pengatur Posisi Katup Burkert 2103 Series. Burkert 2103 Series 19 halaman. Remote-positioner, installation on process valves with internal air flow
Juga untuk Burkert 2103 Series: Petunjuk Tambahan (12 halaman)

Burkert 2103 Series Panduan Memulai Cepat
5.1.4 Tank bottom valve type 2105
Tank bottom valve
with welding flange
VA diaphragm socket
(VA = stainless steel)
Actuator housing
Actuator cover
Transparent cap with
position indicator
Pilot air ports 1 and 2
(see detailed view)
Fig. 4:
Structure and description type 2105
5.2
Function
Spring force (CFA) or pneumatic pilot pressure (CFB and CFI) gen-
erates the closing force on the diaphragm pressure piece. The force
is transferred via a spindle which is connected to the actuator piston.
5.2.1 Control functions (CF)
WARNING!
For control function I: Danger if pilot pressure fails.
For control function I (CFI) control and resetting occur pneumati-
cally. If the pressure fails, no defined position is reached.
▶ To ensure a controlled restart, first pressurize the device with
pilot pressure, then switch on the medium.
8
Second pilot air port
for CFI and air
discharge connection
for CFA and CFB
2
1
Pilot air port 1
for control function
(CF) A, B, I
english
Type 2103, 2104, 2105
Structure and function
A
CFA
Closed by spring force in rest position.
A
P
CFB
Opened by spring force in rest position.
A
P
CFI
Actuating function via reciprocal
pressurization.
P
6

TECHNICAL DATA

WARNING!
Risk of injury from high pressure.
Excessive pressure can damage the device.
▶ Comply with pressure range values on the type label.
6.1
Conformity
Type 2103, 2104 and 2105 conforms with the EU Directives
according to the EU Declaration of Conformity.
6.2
Standards
The applied standards, which verify conformity with the EU
Directives, can be found on the EU-Type Examination Certificate
and / or the EU Declaration of Conformity.
6.3
Type label
Example:
2103 A 20M PTFE VS
Pilot 4,8-10bar
Tamb 0°C - +60°C
Pmed 10,0bar
Tmed xxx°C - +130°C
Da=26,9 s=1,6
00175139
Fig. 5:
Example of type label
CE
W3ZLT