Juga untuk Siemens SIMATIC ET 200S: Panduan Operator (18 halaman), Manual (16 halaman), Panduan Pengguna (16 halaman), Panduan Pengguna (26 halaman), Manual (37 halaman), Manual (24 halaman), Manual Fungsi (40 halaman), Petunjuk Pengoperasian (4 halaman), Petunjuk Pengoperasian Asli (19 halaman), Petunjuk Pengoperasian Asli (20 halaman), Manual (34 halaman), Manual (14 halaman), Manual (24 halaman), Petunjuk Pengoperasian Asli (17 halaman), Petunjuk Pengoperasian Asli (19 halaman), Manual (16 halaman), Manual (12 halaman), Manual (32 halaman), Manual (18 halaman), Manual (12 halaman), Manual (28 halaman), Manual (22 halaman), Manual (22 halaman), Manual (36 halaman), Manual (16 halaman)

Siemens SIMATIC ET 200S Manual
Connecting
5.1 Connecting measuring sensors
Abbreviations used
The meanings of the abbreviations in the figures below are as follows:
M +
M-
M
ANA
M
L+
U
CM
U
ISO
Isolated measuring sensors
The isolated measuring sensors are not connected to the local ground potential. These can
be potential-free. Depending on local conditions or interference, potential differences U
(static or dynamic) can occur between the measuring lines M- of the input channels and the
reference point of the measuring circuit M
In environments with a high level of EMC interference, it is advisable to connect M- to M
in order to prevent the permissible U
The following schematic representation illustrates the connection of isolated measuring
sensors to the analog input modules.
5
24
Measuring line (positive)
Measuring line (negative)
Analog measuring circuit reference potential
Ground connection
Rated load voltage 24 V DC
Potential difference between inputs
Potential difference between M- and central grounding point
mA
mA
4
Logic
Backplane bus
Ground bus
Central grounding point
Isolated measuring sensors
.
ANA
value from being exceeded.
CM
1
3
2AI I 4WIRE HS analog electronic module (6ES7134-4GB62-0AB0)
2
Manual, 01/2008, A5E01076124-02
CM
ANA