Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
4.3

Explanation of the module/channel parameters

Diagnostics, Missing supply voltage L+
Enabling of the diagnostics for missing or insufficient supply voltage L+.
IO redundancy
You can configure two identical modules redundantly. To do so, plug both modules into a
redundant terminal block side by side. You can find additional information on mounting
modules in an IO redundancy configuration in the ET 200SP HA System Manual, section
"Installing", "Installing terminal block".
In IO redundancy mode, the left-hand module is the master and the right-hand module is the
slave.
Both redundant modules measure simultaneously and independently in the process. Both
redundant modules generate diagnostics, alarms and process values.
Diagnostics, Short-circuit to ground
When the digital output is enabled, you can enable diagnostics that report a digital output short
circuit to M.
Diagnostics short-circuit to L+
When the digital output is enabled, you can enable diagnostics that report a digital output short
circuit to L+.
Diagnostics, Wire break
With activated wire break checking, the diagnostics are enabled when the line is from the
actuator is interrupted.
Check for wire break
Enable for wire break check. The I/O module can only detect a wire break if wire-break is
activated.
Channel activated
Specifies whether a channel is activated or deactivated.
Reaction to CPU STOP
Determines the reaction of the digital output to CPU STOP or to failure of communication
between the interface module and CPU.
Digital output module DQ 16x24VDC/0.5A (6DL1132-6BH00-0PH1)
Manual, 05/2017, A5E39265993-AA
4.3 Explanation of the module/channel parameters
Parameters
15