Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (40 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
Image A-3
Codes for measurement types
The following table contains the codes for the measuring types of the analog input module.
You must enter these codes in byte x (see channel parameter block figure).
Table A- 1
Measurement type
Deactivated
Current, 4-wire transducer
Current, 2-wire transducer
Codes for measuring ranges
The following table contains the codes for the measuring ranges of the analog input module.
You must enter these codes in byte x+1 (see channel parameter block figure).
Table A- 2
Measuring range
Current
0 mA to 20 mA
4 mA to 20 mA
±20 mA
Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1)
Manual, 12/2015, A5E36104399-AA
A.2 Parameter assignment and structure of the parameter data record
Structure of bytes x to x+17 for channels 0 and 1
Codes for measurement types
Codes for measuring ranges
Parameter data record
Code
0000 0000
0000 0010
0000 0011
Coding
0000 0010
0000 0011
0000 0100