Juga untuk Siemens SIMATIC ET 200SP: Manual (40 halaman), Panduan Pengguna (21 halaman), Manual (34 halaman), Manual (48 halaman), Manual (30 halaman), Manual (34 halaman), Informasi Produk (38 halaman), Manual (37 halaman), Manual (36 halaman), Manual (44 halaman), Manual (31 halaman), Manual (35 halaman), Manual (23 halaman), Panduan Konfigurasi (20 halaman), Manual (34 halaman), Manual (29 halaman), Manual (33 halaman), Manual (31 halaman), Panduan Pengguna (32 halaman), Manual (31 halaman), Manual (28 halaman), Manual (41 halaman), Manual (32 halaman), Manual (49 halaman), Manual (24 halaman), Manual (34 halaman), Manual (41 halaman), Manual (30 halaman), Manual (31 halaman), Manual (27 halaman), Manual (24 halaman), Manual (24 halaman), Manual (25 halaman), Manual (49 halaman), Manual (38 halaman), Manual (39 halaman), Informasi Produk (24 halaman), Manual (32 halaman), Informasi Produk (10 halaman), Panduan Peralatan (43 halaman), Manual (33 halaman), Panduan Peralatan (44 halaman), Petunjuk Pengoperasian Asli (6 halaman), Manual (35 halaman), Manual (28 halaman), Panduan Peralatan (32 halaman), Manual (50 halaman), Manual (30 halaman), Manual (26 halaman), Manual (28 halaman), Manual (34 halaman), Manual (44 halaman), Manual (33 halaman), Panduan Peralatan (42 halaman), Manual Petunjuk Asli (16 halaman)

Siemens SIMATIC ET 200SP Manual
2.2

Functions

IO-Link is a point-to-point connection between a master and a device. Both conventional and
intelligent sensors/actuators can be used as devices at the IO-Link via unshielded standard
cables using proven 3-wire technology. IO-Link is backward compatible with conventional
digital sensors and actuators. The circuit state and data channel are designed in proven
24 V DC technology.
Reference
Additional information can be found in the IO-Link System
(http://support.automation.siemens.com/WW/view/en/65949252) function manual.
2.3
Replacement of the IO-Link Master CM 4xIO-Link communication
module with an electronic coding element type H
If you remove the communication module from the BaseUnit, part of the electronic coding
element remains in the BaseUnit. The parameters of the IO-Link Master CM 4xIO-Link and
of the IO-Link devices are stored in this part. A newly inserted (but not yet configured)
IO-Link master takes over the parameters from the electronic coding element.
Removal and insertion
Plugging in the IO-Link Master CM 4xIO-Link communication module when the load is
switched on can result in dangerous conditions in your plant.
The ET 200SP distributed I/O system may be damaged as a result.
The IO-Link Master CM 4xIO-Link communication module should only be plugged in or
pulled out when the load is switched off.
Communication module IO-Link Master CM 4xIO-Link (6ES7137-6BD00-0BA0)
Manual, 10/2017, A5E03856846-AD
CAUTION
Product overview
2.2 Functions
13