Juga untuk Siemens SIMATIC ET 200SP HA: Manual (50 halaman), Manual (34 halaman), Manual (38 halaman), Panduan Peralatan (44 halaman), Panduan Peralatan (50 halaman), Panduan Peralatan (38 halaman), Panduan Peralatan (46 halaman), Panduan Peralatan (42 halaman), Panduan Peralatan (44 halaman), Panduan Peralatan (36 halaman), Panduan Peralatan (38 halaman)

Siemens SIMATIC ET 200SP HA Manual
Note
The following LEDs indicate a short-circuit in the backplane bus supply or in the bus connection
supply:
● LED PWR: On
● LED RN, ER and MT: Off
6.2

Interrupts

Diagnostics interrupts
Diagnostic interrupts are used by the IM 155-6 PN HA to signal diagnostic messages as well
as maintenance events, see also appendix Diagnostics messages and maintenance events
(Page 31)
The IM 155-6 PN HA generates a diagnostic interrupt for the following events:
● Faulty 24 V DC power supply
● Module parameter errors or incorrect carrier present in real slot
● Failure of redundancy partner
● Redundancy partners have different hardware/firmware
● Impermissible bus adapter on interface module
● Incorrect bus adapter in redundancy partner
● Defective retentive memory in bus adapter
● Permissible backplane bus size exceeded
● No server module
Diagnostics of I/O modules are forwarded by the IM 155-6 PN HA and depend on the respective
I/O module.
Maintenance messages
The IM 155-6 PN HA generates a maintenance message for the following events:
● Different hardware/firmware in the redundancy partners
● IO redundancy warning
● Redundancy parameter assignment inconsistent
● Retentive memory in carrier module defective
● Defective retentive memory in bus adapter
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Manual, 05/2017, A5E39262148-AA
Displays and interrupts
6.2 Interrupts
23