Juga untuk Siemens SINAMICS G120: Memulai (46 halaman), Panduan Petunjuk Pengoperasian (32 halaman), Memulai (30 halaman), Petunjuk Pemasangan Perangkat Keras (2 halaman), Petunjuk Pemasangan dan Panduan Pemilik (2 halaman), Petunjuk Instalasi (2 halaman), Petunjuk Instalasi (2 halaman), Petunjuk Pengoperasian yang Ringkas (32 halaman), Memulai (50 halaman), Panduan Perangkat (34 halaman), Panduan Pemasangan Cepat (2 halaman), Deskripsi Aplikasi (50 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman), Manual (31 halaman), Manual Aplikasi (34 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman)

Siemens SINAMICS G120 Manual
4 SINAMICS G120 Add-On Instructions
Basic Speed Control –Telegram 1
4.3
4.3.1

Functionality

The G120 Simple Speed Block provides an interface for basic speed control of a
SINAMICS drive via EtherNet/IP. The drive is configured for control using Standard
Telegram Type 1 which presets the drive speed reference and control word to be
sourced from the communication interface.
4.3.2

Schematic Ladder Representation

Figure 4-1
4.3.3

Input and Output Parameters

Table 4-4 Input parameters
Variable Name
G120_Speed_Block
ON_OFF1
OFF2
OFF3
RUN_SET_POINT
FAULT_RESET
RPM_SET_SPEED
MAX_SPEED
SINAMICS G: Control of a G120 with an Allen-Bradley controller
(Compact/ ControlLogix with RSLogix 5000) via EtherNet/IP
Entry-ID: 82843076,
V4.0,
G120 Simple Speed Block
Data Type
Instance Data
BOOL
BOOL
BOOL
BOOL
BOOL
REAL
REAL
09/2018
Description
Drive Enable (ON/OFF1)
1 = Enable Drive
2 = Ramp down and disable drive
Coast Stop Command
0 = Off2 (Immediate disable)
1 = No OFF2 command
Fast Stop command
0 = OFF3 Fast ramp and disable drive
1 = No OFF3 command
Speed setpoint enable
0 = Setpoint disabled
1 = Setpoint enabled
Reset active drive faults
0 = No fault reset
1 = Reset fault(s) on rising edge
Speed setpoint in [rpm]
Speed at 100% setpoint
Must be the same p2000 ( of the drive)
11