Juga untuk Siemens SINAMICS G120: Memulai (46 halaman), Panduan Petunjuk Pengoperasian (32 halaman), Memulai (30 halaman), Petunjuk Pemasangan Perangkat Keras (2 halaman), Petunjuk Pemasangan dan Panduan Pemilik (2 halaman), Petunjuk Instalasi (2 halaman), Petunjuk Instalasi (2 halaman), Petunjuk Pengoperasian yang Ringkas (32 halaman), Manual (42 halaman), Panduan Perangkat (34 halaman), Panduan Pemasangan Cepat (2 halaman), Deskripsi Aplikasi (50 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman), Manual (31 halaman), Manual Aplikasi (34 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman)

Siemens SINAMICS G120 Memulai
Installing
3.3 Installing Control Unit
The factory settings described above for USS and PROFIBUS/PROFINET terminals
correspond to default setting 12 (two-wire control using method 1) or default setting 7
(switchover between fieldbus and jog using DI 3).
See also: Default settings of the terminal strip (Page 28).
3.3.3

Default settings of the terminal strip

Default setting 1: Two fixed speeds
Control Units CU240E-2
Selected with
STARTER: Conveyor technology
with 2 fixed frequencies
BOP-2: coN 2 SP
Fieldbus interface is not active.
DI 4 and DI 5 = high: The inverter adds
both fixed speeds.
Default setting 4: PROFIBUS or
PROFINET
Control Units CU240E-2
Selected with
STARTER: Conveyor systems with
fieldbus
BOP2: coN Fb
PROFIdrive telegram 352
28
Default setting 2: Two fixed speeds
with safety function
Control Units CU240E-2
Selected with
STARTER: Conveyor systems with
Basic Safety
BOP-2: coN SAFE
Fieldbus interface is not active.
Default setting 5: PROFIBUS or
PROFINET with safety function
Control Units CU240E-2
Selected with
STARTER: Conveyor systems with
fieldbus and Basic Safety
BOP-2: coN Fb S
PROFIdrive telegram 352
Default setting 3: Four fixed speeds
Control Units CU240E-2
Selected with
STARTER: Conveyor technology
with 4 fixed frequencies
BOP-2: coN 4 SP
Fieldbus interface is not active.
Multiple DIs = high: The inverter adds
the corresponding fixed speeds.
Default setting 6: PROFIBUS or
PROFINET with two safety functions
CU240E-2 F, CU240E-2 DP-F, and
CU240E-2 PN-F Control Units
Selected with
STARTER: Fieldbus with Extended
Safety
BOP-2: Fb SAFE
PROFIdrive telegram 1
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 04/2014, A5E32885834B AB