Juga untuk Siemens SINAMICS G120: Memulai (46 halaman), Panduan Petunjuk Pengoperasian (32 halaman), Memulai (30 halaman), Petunjuk Pemasangan Perangkat Keras (2 halaman), Petunjuk Pemasangan dan Panduan Pemilik (2 halaman), Petunjuk Instalasi (2 halaman), Petunjuk Instalasi (2 halaman), Petunjuk Pengoperasian yang Ringkas (32 halaman), Manual (42 halaman), Panduan Perangkat (34 halaman), Panduan Pemasangan Cepat (2 halaman), Deskripsi Aplikasi (50 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman), Manual (31 halaman), Manual Aplikasi (34 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman), Petunjuk Pengoperasian yang Ringkas (2 halaman)

Siemens SINAMICS G120 Memulai
Default setting 7: Switch over between fieldbus and jogging using DI 3
Selected with
STARTER: Fieldbus with data set switchover
BOP-2: FB cdS
Factory setting for inverters with PROFIBUS or PROFINET interface
PROFIdrive telegram 1
The CU 240B-2 does not have
terminals 16 and 17
Default setting 9: Motorized
potentiometer (MOP)
All Control Units
Selected with
STARTER: standard I/O with MOP
BOP-2: Std MoP
Fieldbus interface is not active.
The CU 240B-2 does not have
terminals 16 and 17
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 04/2014, A5E32885834B AB
All Control Units
Fieldbus interface is not active.
The CU 240B-2 does not have
terminals 16 and 17
Default setting 12: Two-wire control
with method 1
All Control Units
Selected with
STARTER: Standard I/O with
analog setpoint
BOP-2: Std ASP
Factory setting for inverters with RS485
interface
Fieldbus interface is not active.
The CU 240B-2 does not have
terminals 16 and 17
3.3 Installing Control Unit
Default setting 8: Motorized
potentiometer (MOP) with safety
function
Control Units CU240E-2
Selected with
STARTER: MOP with Basic Safety
BOP-2: MoP SAFE
Fieldbus interface is not active.
Default setting 13: Setpoint via analog
input with safety function
Control Units CU240E-2
Selected with
STARTER: Standard I/O with
analog setpoint and safety
BOP-2: ASPS
Fieldbus interface is not active.
Installing