The WM100 is sensitive to lateral disturbances to its magnetic field. If the WM100 is
responding to motion from an interfering target, move the WM100 or install a ferrous
plate (steel ) as a shield between the WM100 and the interfering target.
Where possible, the probe should be mounted so the conduit entry is pointing down to
avoid accumulation of condensation in the casing. Connection of the probe should be
made via flexible conduit for easier removal or adjustment of the probe.
In climates where direct sunlight may cause the SITRANS WM100
Note:
temperature to rise above the specified limit, shade the unit by installing a sun
shield.
WM100 Circuit Card
WARNING: Disconnect power before opening top cover.
Check nameplate for proper operation voltage (115 V AC or 230 V AC).
Note:
ground terminal for
customer connection
7ML19985MW01
SITRANS WM100 – OPERATING INSTRUCTIONS
detection indicator LED
terminal block for
customer connection
Page 5