Siemens Sivacon S8 Panduan Petunjuk Pengoperasian - Halaman 6

Jelajahi secara online atau unduh pdf Panduan Petunjuk Pengoperasian untuk Beralih Siemens Sivacon S8. Siemens Sivacon S8 9 halaman. Switchboard
Juga untuk Siemens Sivacon S8: Panduan Petunjuk Pengoperasian (7 halaman), Panduan Petunjuk Pengoperasian (24 halaman), Manual (11 halaman), Panduan Petunjuk Pengoperasian (11 halaman), Panduan Petunjuk Pengoperasian (19 halaman), Panduan Petunjuk Pengoperasian (12 halaman), Panduan Petunjuk Pengoperasian (29 halaman), Panduan Petunjuk Pengoperasian (13 halaman), Panduan Petunjuk Pengoperasian (13 halaman), Panduan Petunjuk Pengoperasian (24 halaman), Panduan Petunjuk Pengoperasian (11 halaman), Panduan Petunjuk Pengoperasian (15 halaman), Manual (11 halaman), Panduan Petunjuk Pengoperasian (9 halaman), Dokumentasi Perbaikan (44 halaman), Petunjuk Manual (12 halaman), Panduan Petunjuk Pengoperasian (11 halaman), Panduan Petunjuk Pengoperasian (18 halaman)

Siemens Sivacon S8 Panduan Petunjuk Pengoperasian

1.3 Montagem

O adaptador deve ser inserido no compartimento respetivo da unidade
extraível. Depois, a porta do compartimento deve ser fechada. O con-
dutor PE verde amarelo deve ser aparafusado na unidade extraível e
depois ligado à unidade extraível e ao adaptador a testar utilizando o
cabo de controlo fornecido. Para tal, a ficha de controlo na unidade
extraível deve ser colocada na posição de teste.
Fig. 4: Contacto do cabo na unidade extraível (o condutor PE não é
mostrado)
1.4 Colocação em funcionamento
Ao estabelecer a posição de teste no adaptador localizado na in-
stalação, a unidade extraível a ser testada é agora conectada aos si-
nais de comando do sistema e podem ser realizados medições e cir-
cuitos de teste apropriados.
2 Modo de funcionamento e estrutura da unidade de colo-
cação em funcionamento e teste para unidades extraíveis
pequenas

2.1 Modo de funcionamento

A unidade de colocação em funcionamento e de teste destina-se a
permitir o comando de pequenas unidades extraíveis com ou sem
componentes de bus que devem ser operadas fora da instalação para
trabalhos de colocação em funcionamento e ajuste.
Para este efeito, os sinais de comando são contactados utilizando um
adaptador (1) a ser colocado no compartimento respetivo e ligado a
tomadas no painel de instrumentos (2).
A unidade extraível pequena (3) destinada aos trabalhos de colocação
em funcionamento é colocada em frente da instalação (mesa, carrinho
de laboratório, etc.). Para contactar o circuito de corrente de comando,
é necessária uma reprodução do compartimento (4) na qual a unidade
extraível deve ser inserida. Conectar a reprodução do compartimento
(4) e o adaptador (1) no compartimento por meio de um cabo (5).
O circuito de corrente principal não é contactado.
Fig. 5 / Fig. 5
4
Fig. 4 / Fig. 4
1
2

1.3 Mounting

Insert the adapter into the appropriate withdrawable unit compart-
ment. After that close the compartment door. The green-yellow PE
conductor must be screwed onto the withdrawable unit designated for
the commissioning / tests. Connect this withdrawable unit with the
adapter using the supplied control cable. For this purpose, set the
control plug at the withdrawable unit into the test position.
Fig. 4: Contacting of the cable at the withdrawable unit (PE conduc-
tor isn't shown)

1.3 Commissioning

Due to the setup of the test position at the adapter placed in the
switchboard the withdrawable unit designated for the commission-
ing/tests is now connected with control signals of the switchboard.
The appropriate measurements and test circuits can be executed.
2 Functionality and design of the commissioning and test unit
for Miniature withdrawable units
2.1 Functionality
The commissioning and test unit shall allow the operation of the con-
trolling of the Miniature withdrawable units with and without bus com-
ponents outside of the switchboard for commissioning and configura-
tion operations.
For this purpose, the control signals are contacted via an adapter set
(1) in the appropriate compartment and wired on socket connectors
on the instrument panel (2).
The miniature withdrawable unit (3) designated for the commission-
ing will be placed in front of the switchboard (table, trolley or similar).
For the contacting of the control circuit a compartment replication (4)
is necessary, in which the withdrawable unit is to be placed.
The compartment replication (4) and adapter set (1) are connected
using a cable (5).
The main circuit will not be contacted.
5
4
3
8PQ9801-8AA24