Acuity Controls nLight nPOD 2P Instalasi - Halaman 2
Jelajahi secara online atau unduh pdf Instalasi untuk Beralih Acuity Controls nLight nPOD 2P. Acuity Controls nLight nPOD 2P 2 halaman. Wallpod: 2-channel on/off low voltage
WIRING
TYPICAL WIRING
Power to WallPod device is provided via the CAT-5e connection to an nLight power pack/supply or Bridge. T568B pin/pair assignment is recommended for
all CAT-5e cables.
ON/OFF
CAT-5
GROUND
3-WAY CONFIGURATION WIRING
CAT-5
INSTALLATION
•
Mount WallPod using holes that align with standard single gang switch box or
low voltage ring.
•
Connect green screw to ground.
•
Access RJ-45 ports by sliding trapdoor up.
•
Insert CAT-5 cable(s) through opening and route out through cutouts in rear of
WallPod.
•
Secure cable(s) by sliding trapdoor back into orignal place
•
Interconnect unit with other nLight devices in lighting zone using CAT-5 cables.
•
Once power is received via CAT-5 connection, all devices in zone will
automatically begin functioning together according to each device's defaults.
Attention! Only use non-booted CAT5e cables.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com
© 2014-2016 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/06/16
BLK
ORN
nPP16
LOAD 1
CAT-5C
nPP16
CAT-5
CAT-5
CAT-5
nPP16
CAT-5
-
120 V
-
277 V
nPP16
AT-5
CAT-5
BLK
-
120 V
ORN
-
277 V
LOAD 1
BLK
-
120 V
ORN
-
277 V
LOAD 2
BLK
-
120 V
ORN
-
277 V
LOAD 2
CAT-5
LOAD 1
GROUND
CAT-5
LOAD 2
CAT-5
GROUND
nPODM-2P
2 of 2