Acuity Controls nLight nPOD 2P 설치 - 페이지 2

{카테고리_이름} Acuity Controls nLight nPOD 2P에 대한 설치을 온라인으로 검색하거나 PDF를 다운로드하세요. Acuity Controls nLight nPOD 2P 2 페이지. Wallpod: 2-channel on/off low voltage

Acuity Controls nLight nPOD 2P 설치
WIRING
TYPICAL WIRING
Power to WallPod device is provided via the CAT-5e connection to an nLight power pack/supply or Bridge. T568B pin/pair assignment is recommended for
all CAT-5e cables.
ON/OFF
CAT-5
GROUND
3-WAY CONFIGURATION WIRING
CAT-5
INSTALLATION
Mount WallPod using holes that align with standard single gang switch box or
low voltage ring.
Connect green screw to ground.
Access RJ-45 ports by sliding trapdoor up.
Insert CAT-5 cable(s) through opening and route out through cutouts in rear of
WallPod.
Secure cable(s) by sliding trapdoor back into orignal place
Interconnect unit with other nLight devices in lighting zone using CAT-5 cables.
Once power is received via CAT-5 connection, all devices in zone will
automatically begin functioning together according to each device's defaults.
Attention! Only use non-booted CAT5e cables.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com
© 2014-2016 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/06/16
BLK
ORN
nPP16
LOAD 1
CAT-5C
nPP16
CAT-5
CAT-5
CAT-5
nPP16
CAT-5
-
120 V
-
277 V
nPP16
AT-5
CAT-5
BLK
-
120 V
ORN
-
277 V
LOAD 1
BLK
-
120 V
ORN
-
277 V
LOAD 2
BLK
-
120 V
ORN
-
277 V
LOAD 2
CAT-5
LOAD 1
GROUND
CAT-5
LOAD 2
CAT-5
GROUND
nPODM-2P
2 of 2