AEMC instruments JM852 Panduan Pengguna - Halaman 4

Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Alat Ukur AEMC instruments JM852. AEMC instruments JM852 4 halaman. Ac current probe

OPERATION
Please make sure that you have already read and fully understand the WARNING section on page 1.
Making Measurements with the AC Current Probe Model JM852
• Connect the black and red terminals to the Voltage AC range of your DMM or voltage measuring
instrument. Select the appropriate voltage range (2V AC). Clamp the probe around the conductor to be
tested. If the reading is less than 200 mV, select the lower range until you obtain the best resolution.
Read the value display on the DMM and multiply it by the probe ratio (3000/1 = 3000). (If reading =
0.592V AC, the current flowing through the probe is 0.592 x 3000 = 1776A).
• For best accuracy: carefully center the conductor inside the probe jaw, avoid if possible, the proximity of
other conductors which may create noise.
Tips for Making Precise Measurements
• When using a current probe with a meter, it is important to select the range that provides the best
resolution. Failure to do this may result in measurement errors.
• Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air
gaps between the jaws, increasing the phase shift between primary and secondary. It is very critical for
power measurement.
MAINTENANCE:
Warning
• For maintenance use only original replacement parts.
• To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so.
• To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents
into the probe.
Cleaning
To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times.
Failure to do so may result in error in readings. To clean the probe jaws, use a very fine sand paper (fine
600) to avoid scratching the jaw, then gently clean with a soft oiled cloth.
REPAIR AND CALIBRATION
You must contact our Service Center for a Customer Service Authorization number (CSA#). This will
ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA#
on the outside of the shipping container.
Chauvin Arnoux
15 Faraday Drive  Dover, NH 03820 USA
(800) 945-2362 (Ext. 360) • (603) 749-6434 (Ext. 360) • [email protected]
(Or contact your authorized distributor)
NOTE: All customers must obtain a CSA# before returning any instrument.
TECHNICAL AND SALES ASSISTANCE
If you are experiencing any technical problems, or require any assistance with the proper use or
application of this instrument, please contact our technical hotline:
(800) 343-1391 • (508) 698-2115 • [email protected]
LIMITED WARRANTY
The current probe is warranted to the owner for a period of one year from the date of original purchase
against defects in manufacture. This limited warranty is given by AEMC
distributor from whom it was purchased. This warranty is void if the unit has been tampered with, abused
or if the defect is related to service not performed by AEMC
Full warranty coverage and product registration is available on our website at:
www.aemc.com/warranty.html.
Please print the online Warranty Coverage Information for your records.
®
®
, Inc. d.b.a. AEMC
Instruments
®
Instruments.
®
Instruments, not by the
99-MAN 100126.v4 07/13