Dinel RFLS-53N Buku Petunjuk - Halaman 11

Jelajahi secara online atau unduh pdf Buku Petunjuk untuk Tingkat Laser Dinel RFLS-53N. Dinel RFLS-53N 16 halaman. High frequency level switch

Setting modes
The sensor can be set to normally closed "O-mode" or to normally open "C-mode" switch types.
level state
level state
For safety reasons, for scanning min. level, we recommend you to use the "O" mode setting (sensor closes when
submerged). A faulty sensor or wiring will take effect here in the same way as level emergency conditions by opening
the sensor. Analogously for the max. level, we recommend you to set the "C" mode (sensor opens when submerged).
© Dinel, s.r.o.
RFLS–53
mode
output state
O
CLOSED
O
OPEN
mode
output state
C
OPEN
C
CLOSED
Orange LED
(shining)
(dark)
Orange LED
(dark)
(shining)
11