4.4 Condensed Aerosol Generator monitoring Test
Step 14
Step 15
Step 16
Step 17
Step 18
Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Disconnect one of the test lamps and ensure that the yellow Fault LED on
the front panel and the internal yellow LED marked LED5 are lit and the
buzzer sounds.
Press the Silence Buzzer button and ensure the buzzer silences.
Re-connect the test lamp and ensure that the fault indications clear.
Turn the Isolate Key Switch to the "Off" position and ensure the that the
yellow fault LED on the front panel and the internal yellow LED marked
LED5 are lit and the buzzer sounds.
Turn the Isolate Key Switch to the "Live" position and ensure that the
fault indication clears.
Page 13 of 18