5. Testing and Commissioning
5.1 System test
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Step 8
Step 9
Step 10
Step 11
Step 12
Step 13
Step 14
Step 15
Step 16
Step 17
Step 18 Re-connect the test lamp and ensure that the fault indication clears.
Step 19
Turn Isolate Key Switch to "Off" position and ensure that the yellow Fault
Step 20
Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Power off the unit.
Turn the Isolate Key Switch to the "Off" position.
Remove the front frame panel.
Disconnect the FirePro Generators and ensure the test lamps are fitted to
the terminals.
Inspect all components – detectors, sirens etc.
Inspect cables for signs of damage.
Inspect panel fuse and check if it has blown.
Power on the unit.
Turn Isolated Key Switch to the "Live" position.
Trigger the detection input by operating a smoke detector linear heat
detector.
Ensure that the test lamps connected to the FirePro GEN1 terminals light
immediately, the red fire indicator on the panel is lit, the yellow fault
indicator is lit and the buzzer sounds.
Press the Silence Buzzer button to silence the buzzer and then the Reset
button to reset the system.
Disconnect the wiring to the detector and ensure that the yellow Fault LED
on the front panel and the internal yellow LED marked LED4 are lit and the
buzzer sounds.
Press the Silence Buzzer button and ensure the buzzer silences.
Re-connect the detector wiring and ensure that the fault indication clears.
Disconnect one of the test lamps and ensure that the yellow Fault LED on
the front panel and the internal yellow LED marked LED5 are lit and the
buzzer sounds.
Press the Silence Buzzer button and ensure the buzzer silences.
LED on the front panel and the internal yellow LED marked LED5 are lit and
the buzzer sounds.
Turn Isolate Key Switch to "Live" position and ensure that the fault
indication clears.
Page 14 of 18