Figure 6- Connection to Condensed Aerosol Generator
3.4 FIRE contacts for remote signalling
Volt free changeover contact that will operate whenever the system is triggered to
alarm. This contact is rated for a maximum of 30V DC and 1 Amp. These ratings must
not be exceeded.
3.5 FAULT contacts for remote signalling
Volt free changeover contact that will operate whenever there is a fault condition. This
contact is rated for a maximum of 30V DC and 1 Amp. These ratings must not be
exceeded.
3.6 Sounder circuit wiring
There is no dedicated Siren circuit on this FPC-2V2 panel, however a siren can be
connected to the fire relay output. The "FIRE" terminal on the FPC-2V2 panel is a relay
that creates a closed circuit upon activation of the panel. This can be used to activate a
siren or other device when wired as shown in Figure 7.
Figure 7- Connection to Sounder/Strobe
Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual