3.7 Connection to addressable modules

It is possible to configure the FPC-2V2 panel such that it will trigger a VMMI1000
addressable module with fire and fault signals via FIRE and FAULT relay contacts.
To make the FPC-2V2 panel compatible with an addressable input module, move jumpers
J1 and J2 from their default positions (position A) to position B.
The FIRE NO and C terminals can now be connected directly to the addressable input
module as shown in Figure 8.
Alarm and Fault conditions will be indicated on a suitable address fire alarm control panel.
Note:
The volt free contacts cannot be used for anything else when the contacts are connected
to an addressable input module.
Figure 8- Connection from FPC-2V2 to VMMI1000 addressable modules