6.9 Impulse rate

Adjust. values:
Antifr. type
Flow. measurem.
Volume/Imp.

6.10 Subaddress

Adjust. values:
Flow measurem.
Volume/Imp.
Subaddress

6.11 Bus mode

Adjust. values:
Volume/Imp.
Subaddress
Bus mode

6.12 Bus master

Adjust. values:
Subaddress
Bus mode
Bus master?

6.13 Sensor offset

Adjust. values:
Bus master?
Sensor 1
Sensor 2
This adjustment channel depends on the selected flowmeter
type.
Water
If the flowmeter V40 is used, the value is indicated in L/I
V40
("Volume/Imp" is indicated on the display).
1,0 L/I
adjustment range: 0.1 ... 99.9 L/I
If the flowmeter type VTP is used, the value is indicated in
I/L ("heat" appears on the display)
adjustment range: 1 ... 2000 I/L
note:
Pay attention to the indicated l/Imp on your flowmeter!
Adjustment of the subaddress. An individual module address
for one iSolar WMZ can be adjusted. This way it is possible
V40
to use several iSolar WMZ with an individual address in one
1,0 L/I
system. If several iSolar WMZ (up to max. 16) are connected
0
to a PC or a datalogger, the calorimeters have to be num-
bered serially, starting with 0. The connection sequence at
the VBus
adjustment range: 0 ... 15
Change of the bus mode: active, passive, or cascaded.
Do not change the factory setting if the iSolar WMZ is
1,0 L/I
connected to acontroller with VBus
0
responds to the bus mode "passive").
Cascaded
Select bus mode "active", if the iSolar WMZ is not connected
to a controller and if data are recorded on a PC or datalogger.
Select bus mode "cascaded", if several iSolar WMZ are con-
nected to a PC or datalogger. The iSolar WMZ modules are
linearily numerated starting with 0 (see 5.9).
• active
• passive
• cascaded
The item "bus master" only appears when subadress "0" and
bus mode "cascaded" have been selected.
0
Select bus master "No" when several iSolar WMZ modules
Cascaded
are cascaded and used along with a controller.
Yes
Select bus master "Yes" when several iSolar WMZ modules
are cascaded and used without a controller..
In order to offset the sensors, an individual offset can be
allocated to each sensor (range -5.0 K ... +5.0 K, in steps of
Yes
0.1 K).
0,0 K
0,0 K
®
is arbitrary.
®
output terminal (cor-