Distech Controls Allure ECB-103 Panduan Instalasi - Halaman 7
Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Pengontrol Distech Controls Allure ECB-103. Distech Controls Allure ECB-103 16 halaman.
Juga untuk Distech Controls Allure ECB-103: Panduan Instalasi (16 halaman)
![Distech Controls Allure ECB-103 Panduan Instalasi](/uploads/products/server2/782496/782496.jpg)
Controller:
ECB-600
ECL-600
Figure 9:
Setting the EOL Terminations on the Allure EC-Smart-Vue Sensor for ECB-600 or ECL-600 Series controllers
When ECx-400 Series I/O Extension Modules are installed with an ECB-600 or ECL-600 Series controller and with Allure Series Communicating Sen-
sors, only the EOL terminations on the last I/O Extension Module and the last Allure Series Communicating Sensor are set to ON. The ECB-600 /
ECL-600 and all other I/O Extension Modules and Allure Series Communicating Sensor s must have their EOL terminations set to OFF.
Figure 10:
Setting the EOL Terminations on the ECx-400 Series Subnetwork Bus when Allure EC-Smart-Vue Sensors are used
ECx-400 Series devices and Allure EC-Smart-Vue sensors are factory-set with the EOL set to OFF by default.
If inserting multiple wires in the terminals, ensure to properly twist wires together prior to inserting them into the terminal connectors.
For more information and detailed explanations on network topology and wire length restrictions, refer to the Network Guide, which can be downloaded
from our website
www.distech-controls.com
Inside
Controller
EOL OFF
EOL ON
For the controller, set the
Subnetwork EOL to ON
Typical Compatible
Controller
ECx-4xx
I/O Extension Modules
- Last daisy-chained I/O Extension Module:
EOL Jumper is ON
- All other I/O Extension Modules:
EOL Jumpers are OFF
Communicating Sensor Sub-Network Bus
- Cat 5e Cable with RJ-45 Connectors
- Last daisy-chained Communicating Sensor:
EOL Jumper is ON
- All other Communicating Sensors:
EOL Jumpers are OFF
.
Cat 5e Cable Subnetwork Bus
EOL set to ON
at the last
sensor at the
end of the Bus
ECx-4xx
I/O Extension Modules
2 - Wire Shielded
ON
OFF
Back of
Allure EC-Smart-Vue
Sensor
ON
OFF
EOL OFF
EOL ON
7 / 16