ESI ESRTP5 Panduan Petunjuk Instalasi - Halaman 13
Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Termostat ESI ESRTP5. ESI ESRTP5 18 halaman. Programmable room
thermostat
Juga untuk ESI ESRTP5: Petunjuk Pengguna (20 halaman)

Menu Technical Settings (tEcH)
3.2
1. Press and hold
until the display shows tInE. Turn the
dial until display shows tEcH then press
&
together
to enter.
2. Use the dial to choose between the below, then press
to enter:-
dS: Delayed Start. Default is OFF. Use the dial to choose
between OFF (function disabled) or ON (heating on time
is delayed up to 40 minutes according to current room
temperature).
tPI: TPI. Default is OFF. Use the dial to choose between
OFF (function disabled), 3CYC (each hour has 3 heating
cycles, recommended for oil boilers) or 6CYC (each hour
has 6 heating cycles, recommended for gas boilers).
SUG: Swing. Default is 0.5. Use the dial to choose
between 0.5-2.0.
AdJ: Temperature calibration. Default is 0. Use the dial to
choose between -3.0°C-3.0°C.
noP: Number of time and temperature events. Default
is 4. Use the dial to choose between 4 or 6 time and
temperature events.
SEr: Landlord Service Interval. Default is OFF.
See section 9 to amend.
13