6. Connect FACP output to the desired AL800LGK9E logic board inputs, and notification appliances to the
desired AL800LGK9E logic board outputs (see Application Guide).
Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with
synchronization capability.
7. For connection of smoke detectors, digital dialer see Optional Hookup Diagram, pg. 8.
Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:
• For all Class B, Style W, X, Y hookups SW1 and SW2 on the AL800LGK logic board must be turned OFF.
For all Class A, Style Z hookups SW1 and SW2 on the AL800LGK logic board must be turned ON.
Function
Input to Output
Follower Mode
Temporal Code 3 Mode
Steady Mode
For the above modes DIP Switch 4 determines which Input controls the
corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Function
Amseco
Sync Mode*
Faraday
Sync Mode*
Gentex
®
Sync Mode*
Gentex is a registered
trademark of
Gentex Corporation.
System Sensor
®
Sync Mode*
System Sensor is a
registered trademark of
Honeywell.
®
CooperWheelock
Sync Mode*
CooperWheelock is a
registered trademark of
Cooper Wheelock.
*Note: The AL1002ULADAJ will only synchronize horns, horn/strobes and strobes that contain synchronization
capability. Contact signal manufacturer for more detailed info.
The same synchronization mode must be selected for all outputs
Note: It is required to control visual notification appliances (strobes) via Input 1 (IN1) and audible
notification appliances (horns) via Input 2 (IN2). This allows audible notification appliances (horns)
to be silenced while visual notification appliances (strobes) continue to operate.
- 4 -
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Switch Positions
ON
OFF
1
2, 3
3
1, 2
1, 2, 3
Sync Mode Selection Table:
Switch Positions
ON
OFF
1, 3,
2
4
2, 4
1, 3
1, 2,
3, 4
1, 2, 4
3
2, 3, 4
1
Descriptions
Output follows signal it receives from the corresponding
input (i.e. FACP Sync module - maintains synchronization
of notification appliance circuit).
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
A steady output signal will be generated.
This mode will accept steady or pulsing input.
Descriptions
This mode is designed to work with the Amseco series of horns,
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and silencing the horns of the horn/strobe combination over
a two-wire circuit while leaving strobes active.
This mode is designed to work with the Faraday series of horns,
strobes, and horn/strobes to provide a means of synchronizing the
Temporal-coded horns, synchronizing the flash timing of the strobe,
and silencing the horns of the horn/strobe combination over a two-
wire circuit while leaving strobes active.
This mode is designed to work with the Gentex
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
This mode is designed to work with the System Sensor
horns, strobes, and horn/strobes to provide a means of synchroniz-
ing the Temporal-coded horns, synchronizing the one-second flash
timing of the strobe, and silencing the horns of the horn/strobe
combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the CooperWheelock series of
horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash tim-
ing of the strobe, and silencing the horns of the horn/strobe combina-
tion over a two-wire circuit while leaving strobes active.
AL800LGK9E Board
Output DIP Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
®
series of horns,
®
series of
AL1002ULADAJ