Altronix AL1002ULADAJ Panduan Instalasi - Halaman 6

Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Pemanjang Altronix AL1002ULADAJ. Altronix AL1002ULADAJ 17 halaman. Nac power extenders
Juga untuk Altronix AL1002ULADAJ: Manual Aplikasi (8 halaman), Manual Aplikasi (8 halaman), Manual Aplikasi (8 halaman)

Altronix AL1002ULADAJ Panduan Instalasi
Power Supply Board*
Terminal
Function/Description
Legend
L, N
Connect 120VAC to these terminals: L to hot, N to neutral (Fig. 3, pg. 8).
+ DC –
24VDC @ 10A in alarm non power-limited output (Fig. 3, pg. 8).
Form "C" dry contacts used to instantaneously signal the loss AC to local annunciation devices,
AC FAIL
with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC
NO, C, NC
occurs terminals marked NO and C are closed, NC and C are open.
Form "C" dry contacts used to instantaneously signal the loss AC to local annunciation devices,
AC LOCAL
with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC
NC, NO, C
occurs terminals marked NO and C are closed, NC and C are open.
Form "C" dry contacts used to signal low battery voltage or loss of battery voltage. Under nor-
BAT FAIL
mal conditions terminals marked NO and C are open, NC and C are closed. During a trouble
NO, C, NC
condition terminals marked NO and C are closed, and NC and C are open (Fig. 3, pg. 8).
– BAT +
Stand-by battery input (leads provided) (Fig. 3, pg. 8).
*Power Board Parameter Specifications:
• AC Fail condition will report approximately 2 hours after loss of AC. To set AC Delay to 1 minute power
the unit down (AC supply and Battery) prior to changing switch position.
Turn "AC Delay" switch ON for 1 minute or OFF for 2 hours, respectively.
• Low battery condition will report at approximately 20VDC.
• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or
removed). A restored battery will report within 30 seconds.
Power Supply Board
Red (DC)
Green (AC)
ON
ON
ON
OFF
OFF
ON
OFF
OFF
AL800LGK9E - Logic Board
LED
OFF
Output 1
Normal
Output 2
Normal
Output 3
Normal
Output 4
Normal
Input 1
Normal
Input 2
Normal
Fault
Normal
*
Indicates current trouble condition. When trouble (open, short or ground) occurs on a specific output, the
corresponding red output LED, [OUT1-OUT4] will blink. The corresponding green input LED will
blink as well. Loop trouble will report within 30 seconds.
** Indicates trouble condition memory. When a trouble condition restores, the units red output LED,
[OUT1-OUT4] will blink with a shorter and distinctly a different duration.
The green input LEDs will be off (normal condition).
To reset the memory depress the reset button (Fig. 3c, pg. 8). The LED(s) will extinguish.
Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit.
- 6 -
Terminal Identification Table:

LED Diagnostics:

Power Supply Status
Normal operating condition.
Loss of AC. Stand-by battery is supplying power.
No DC output.
Loss of AC. Discharged or no stand-by battery. No DC output.
ON
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
BLINK (LONG)*
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
BLINK (SHORT)**
Trouble Condition Memory
Trouble Condition Memory
Trouble Condition Memory
Trouble Condition Memory
AL1002ULADAJ