Amprobe AMB-50 Manuale d'uso - Pagina 15

Sfoglia online o scarica il pdf Manuale d'uso per Apparecchiature di prova Amprobe AMB-50. Amprobe AMB-50 17. 5000v insulation resistance tester

Amprobe AMB-50 Manuale d'uso

SPECIFICATIONS

Safety and Compliances
Certification
Compliances
IEC 61010 CAT.III 600V overvoltage and double insulation standard

Physical Specifications

Display (LCD)
Operating Temperature
Storage Temperature
Relative Humidity
Battery Type
Dimensions (H x W x L)
Weight

General Specifications

Range
Overloading
Battery Indicator
Icon Display
Current Consumption

Feature Summary

Display Backlight
Computer connection
Data Logging and Recall
Autorange
Warning
Voltage
COMP Measurement
PI Measurement
TIME
Digital: 1999 counts
Analog bar graph.
0°C~40°C (32°F ~104°F )
-20°C ~60°C (-4 °F~152°F )
85% @ -10°C ~40°C below;
90% @ 0°C ~40°C :
8pcs X 1.5V (LR14) batteries or power adaptor (input voltage 230V, 50/60Hz,
75mA, input DC14V, 1.0A).
Power adaptor is not included
202 x 155 x 94 mm
Approx. 2kg (4.4 Lbs) (including battery)
Auto
Display OL on insulation resistance range
Display
Equips with function and battery indicator icons.
Maximum: around 1.0A
Average: around 20mA
Bright backlight for clear readings in poorly lighted areas.
Via USB interface.
18
The Meter automatically selects best range
and red light will on.
Auto release voltage
Use the Compare function to set a pass/fail compare level for the insulation
measurements.
Polarization Index is the ratio of insulation resistance. You can pre-set two point
of times and automatically carry out the measurement.
To carry out measurement by setting a specified time within 15 minutes.
10