Indoor Heat Exchanger
Step
4
Slightly pull out the
auxiliary piping.
5
Unfasten the 2 hooks
on the left side.
6
Unfasten the 2 hooks
on the right side.
7
Pull the indoor heat
exchanger to the front
side, unfasten the
hooks completely, and
then remove the indoor
heat exchanger.
14
Procedure
Auxiliary piping
Hook
Indoor heat exchanger
Points
(R23430)
Hook
(R13231)
(R13232)
(R2802)
Removal Procedure
Si041254EE