DSPM Power Lynx 1 Specifiche tecniche - Pagina 2

Sfoglia online o scarica il pdf Specifiche tecniche per UPS DSPM Power Lynx 1. DSPM Power Lynx 1 10.

1.3 SUBMITALS
A. Submittals for engineering approval shall contain the following
1. Installation Drawings: Indicate electrical characteristics and connection require-
ments. Provide cabinet dimensions; battery type, size, dimensions, and weight and
location of conduit entry and exit; single-line diagram, control, and external wiring
requirements; heat rejection and air flow requirements.
2. Product Data: Provide catalog sheets and technical data sheets to indicate phys-
ical data and electrical performance, electrical characteristics, and connection re-
quirements.
B. Upon delivery of the UPS system the following submittals shall be included:
1. An operators and users manual showing safe and correct operation of all
UPS functions.
1.4 QUALIFICATIONS & QUALITY ASSURANCE
A. Manufacturers Certification: The manufacturer shall specialize in manufacturing
of on-line, double conversion, single phase UPS modules specified in this docu-
ment with a minimum of twenty years documented experience, and with a nation
wide service organization. The manufacturer will use only patented ECM technolo-
gy. The manufacturer shall comply with ISO 1001 and shall be designed to interna-
tionally accepted standards.
B. Factory Testing: Prior to shipment the manufacturer shall complete a document-
ed test procedure to test all functions of the UPS module and batteries (via a dis-
charge test) and guarantee compliance with the specification. The manufacturer
shall provide a copy of the test report upon request.
C. Materials and Assemblies: All materials and parts comprising the UPS shall be
new, of current manufacture, and shall not have been in prior service, except as
required during factory testing. All active electronic devices shall be solid state and
not exceed the manufacturers recommended tolerances for temperature or current
to ensure maximum reliability. All semiconductor devices shall be sealed. All relays
shall be provided with dust covers. The manufacturer shall conduct inspections on
incoming parts, modular assemblies and final products.
Title: Micro
02
Doc No.: 018-1000-02
Description: Emergency Lighting Inverter User's Manual
Phone :
Fax:
Rev: NR
Website:
Date: 07/26/2016
E-Mail:
1.877.DSPM.POWER
-
1.877.377.6769
909.930.3335
www.dspmanufacturing.com