Consort SLPBWIFI Manuale di installazione e controllo - Pagina 7

Sfoglia online o scarica il pdf Manuale di installazione e controllo per Controllore Consort SLPBWIFI. Consort SLPBWIFI 8. Wireless controller

7
20. Choosing a position in a room
Before choosing position in the
room check that WIFI signal is pre-
sent in the area. The controller re-
quires a good internet connection.
The SLPBWIFI controller must be fixed to the wall
installed ideally in a plastic surface or recessed
back box. Avoid areas with draught or direct
sun.
Do not position the controller above or
close to the heaters or other heat sources.
Damp areas or areas where SLPBWIFI can be
mechanically damaged should also be avoid-
ed. Avoid
installing the controller in areas
where there are metal objects between the
heater and the controller. This will reduce the RF
range. Also installing the controller in a metal
back box will affect the RF range. The RF range
in ideal conditions can be up to 20m however
this can be reduced when the signal is passing
through the walls or other objects. The range
can be also affected where the controller is
mounted close to power cables, motors or
equipment producing a strong electromagnetic
field. If the temperature control feature is used it
is necessary to use one controller for each room
or zone.
-
21. Installation
The controller is designed to fit onto most single
gang back boxes. When a metal box is used this
must be earthed. The controller is powered by 230
- 240VAC 50Hz. The power consumption is less
than 1W.
The maximum size wire that can be
used is 1mm2, this can be twin and earth or stand-
ard flex . Do not overtighten the connector
screws. Take care not to damage the compo-
nents when connecting the cables.
WARNING, the controller is not
compatible with single gang metal
back box with 4 fixing lugs.
22. Connection to the Main Supply
Electrical installation should be carried out by a
competent installer in accordance with the latest
edition of the IEE Wiring Regulations, (BS.7671),
and any relevant Local Authority Bye-Laws.
This heater must be permanently connected to
the electricity supply via a double pole switch
having 3mm gap on each pole. There are no ex-
ceptions.
A switched Fused Connection unit to BS.1363. Part
4 is a recommended mains supply connection
accessory to ensure compliance with safety re-
quirements applicable to fixed-wiring installation.