9. FIELD SERVICE TESTS
NOTE: Before testing, notify the central station that the detector system is
undergoing maintenance in order to prevent unwanted alarms. Testing the
detector will activate an alarm and send a signal to the panel. The test functions
cannot be used if the detector has a trouble or end-of-life condition. Detectors must
be tested after installation and following periodic maintenance.
The detector has two test buttons, one for smoke testing and one for CO testing
(See Section 2.1 Figure 1).
Anti-Tamper
Locking Tab
Removed
Figure 17 - Anti-Tamper locking tab removed
9.1 SENSITIVITY CHECK
Examine the detector and observe the LED, if the LED is blinking GREEN once every
12 seconds the detector is operating normally and sensitivity is within the marked
sensitivity range on the back of the detector. If the LED is blinking YELLOW every 8
seconds and beeping every 48 seconds it may no longer be within the marked
sensitivity range and should be cleaned. Refer to Section 10.1 for cleaning your
detector.
9.2 SMOKE ALARM TEST
Press and hold the fire test button (See Section 2.1 Figure 1) for 2 seconds, the
detector will sound Temporal-3 and the LED will blink RED along with the sounder.
Continue to press and hold the fire test button for up to 12 seconds to ensure the
smoke alarm signal is sent to the control panel. Verify the signal was received at
the control panel.
9.3 SMOKE ALARM FUNCTIONAL TEST
Using SDi SOLO A10, SDi Smoke Centurion or SDi Smoke Sabre canned smoke
products, according to the labeled instructions, spray canned smoke at the
detector. The detector will sound Temporal-3, the LED will blink RED along with
the sounder and the smoke alarm signal will be sent to the control panel. Verify the
signal was received at the control panel.
9.4 HEAT ALARM FUNCTIONAL TEST
Using a hair dryer of 1000-1500 Watts at a distance of approximately 12 inches
from the detector, direct hot air at the detector. The detector will sound Temporal-
3, the LED will blink RED along with the sounder and the heat alarm signal will be
sent to the control panel.
9.5 CO ALARM TEST
Press and hold the CO test button (See Section 2.1 Figure 1) for 2 seconds, the
detector will sound Temporal-4 and the LED will blink RED along with the sounder.
Continue to press and hold the CO test button for up to 12 seconds to ensure the CO
alarm signal will be sent to the control panel. Verify the signal was received at the
control panel.