2.3 DETECTOR MOUNTING BASE
Tamper Switch
Mechanism
Screw Mounting Holes
Figure 3 - Mounting Base
3. CONTENTS OF BOX
• Wireless Combination Smoke, Heat and Carbon Monoxide Alarm with
mounting base
• Installation guide (APD0812)
• Pack of screws and anchors
• Labels or decals as appropriate
• 2 CR123A Panasonic batteries or 2 EL123AP Energizer batteries
4. OPERATION
The Wireless Combination Smoke, Heat and Carbon Monoxide Detector contains a
sounder which generates ANSI S3.41 Temporal-3 pattern when fire is detected or
ANSI S3.42 Temporal-4 pattern when Carbon Monoxide is detected. In alarm, a
message is also sent to the control panel and the detector's ID is displayed. During
an alarm condition, pressing either of the FIRE or CO test/hush buttons will silence
the sounder for a short period (see LED and sounder operating modes table).
A multi-color LED indicator provides visual indication for the detector operating
modes and states. In general, RED is used to indicate ALARM conditions, YELLOW
is used to indicate FAULT conditions and GREEN is used for normal operation (see
Detector Status LED & Sounder operating modes table).
4.1 DETECTOR STATUS LED & SOUNDER OPERATING MODES
Status
Smoke Alarm
Heat Alarm
Anti-Tamper
Locking Tab
CO Alarm
CO GO/NO-
GO Test
Freeze
Warning
Description
LEDs
3 RED flashes
Smoke has been
in time with
detected
sounder
3 RED flashes
Heat has been
in time with
detected
sounder
4 RED flashes
Carbon Monoxide
in time with
has been detected
sounder
Test mode for
1 GREEN flash
checking Carbon
followed by
Monoxide
1 BLUE flash
functionality with
every 12
test gas
seconds
3 YELLOW
Temperature is
flashes
below 41°F (5°C)
every 4
seconds
Sounder
Temporal-3
BEEP-BEEP-BEEP-pause
(press either button to
hush for 7 minutes)
Temporal-3
BEEP-BEEP-BEEP-pause
Temporal-4
PIP-PIP-PIP-PIP-long
pause
(press either button to
hush for 5 minutes)
None
None