4EVAC IMPACT Manuale d'uso - Pagina 10
Sfoglia online o scarica il pdf Manuale d'uso per Attrezzatura di sicurezza 4EVAC IMPACT. 4EVAC IMPACT 14. Controller
Anche per 4EVAC IMPACT: Manuale di riferimento (8 pagine)
Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
CONTROLLER user manual
Relay outputs
The Controller features 4 potential-free relay outputs to external devices. Each output has individual 3 pins:
normally open,
normally closed,
common.
4.11.1. EVAC
Activated (closed) during EVAC mode, where at least one zone of the voice evacuation system is
transmitting an automatic EVAC message or LIVE EVAC signal from a fireman microphone.
4.11.2. FAULT
Activated (closed) while the fault status is reported by the voice evacuation system. Also activated when
the Controller is not powered.
4.11.3. RESET
Activated (closed) immediately after a manual reboot of the system is triggered on the front panel. The
active pulse length of the reset signal is configurable from 0 (disabled) to 5000ms in the configuration
settings.
4.11.4. USR DEF
This relay output is not in use.
EVAC inputs
There are 16 monitored inputs dedicated to triggering signals for evacuation, silence and reset instructions
from an external fire detection system, as well as any other events, including commercial activities.
Each of these inputs has 1 triggering pin, with a common ground level for all inputs. EVAC inputs have built-
in DC monitoring which requires two resistors of 4.7kΩ + 10kΩ in order to detect input active/inactive states
as well as short and open faults. The EOL resistors must be located directly at the triggering output inside
of the external device (i.e. fire detection system) to provide reliable surveillance of the entire link.
EVAC inputs must receive an activation signal of at least 100ms in order to trigger events. Pulses shorter
than 100ms will be ignored.
Author:
Page 10 of 14
DD