6.4
Alarm inputs
The alarm transmitter can either be digital and trigger an alarm when open or closed or analog,
balanced at 4.7kΩ. A number of typical installations are described below.
Figure 4 – Normally open/closed relays
Figure 5 – Balanced analogue
Figure 6 – Voltage of +5V to +12V with
limiting
Figure 7 – Voltage of -12V to -5V
1. Normally open/closed relays
When connecting the digital signals to trigger an
alarm when opening or closing, the inputs are
connected as such.
This connection can keep the control panel
galvanically isolated from the alarm transmitter.
2. Balanced analogue
If the signals that are sent to the alarm transmitter
are analogue, balanced at 4.7kΩ, the resistor is to
be mounted as such.
This connection can keep the control panel
galvanically isolated from the alarm transmitter.
3. Voltage of +5V to 12V with limiting
In some cases voltage must be limited on the
alarm port in the alarm transmitter in option 3. If
that is the case, insert a 5.1V Zener diode as
illustrated in the sketch.
This connection can keep the control panel
galvanically isolated from the alarm transmitter.
4. Voltage of -12V to -5V
The connection works no matter whether the
output from the control panel is low ohmig
(<500Ω) or high ohmig (>500Ω) when there is an
absence of voltage.
This connection galvanically couples the control
panel and the alarm transmitter.