AddSecure Tor V Manuale di installazione - Pagina 12

Sfoglia online o scarica il pdf Manuale di installazione per Trasmettitore AddSecure Tor V. AddSecure Tor V 20. Alarm transmitter

AddSecure Tor V Manuale di installazione
Connection: Connect relay 4 with pin 12 (normally open) and pin 10 (common) to the alarm
panel at the appropriate input so that the alarm panel can detect a short circuit/open circuit
on the connection.
Status: Normal.
The relay is opened when all fire alarms have been reset and acknowledged from the
alarm receiver.
Status: Alarm in progress
The relay closes then fire are in progress.
6.6

Ethernet connection (broadband)

Whenever Ethernet is included in the service, ETH0 is to be connected to Internet or the
customer network for external communications for the service.

6.6.1 Firewall configuration

All communication, keep state, is initiated by the alarm transmitter to the service platform.
FROM
TO
(Sender)
(Listener)
Tor V
85.117.160.240/28,
85.117.163.239,
85.117.163.240/28
85.117.160.240/28 corresponds to:
85.117.160.240 – 85.117.160.255
6.7

Wireless connection

The alarm transmitter is equipped with an FME male connector for an external antenna. The
external antenna is to be equipped with an FME female connector.
6.8

Reading the signal strength

The signal strength can be read when the alarm transmitter's power supply is restored after an
absence of voltage. The LED status indicates the current strength in four steps. The highest
value indicates the current signal strength. For more details, see the appendix.
INDICATOR
SIGNAL STRENGTH
LED A
>25
LED B
20–25
LED C
14–19
LED D
0–13
To return to normal mode, press the opening tamper switch for five seconds or put on the
cover so that the switch for the opening tamper is pushed down.
Note that the alarm transmitter does not work when you are reading the
signal strength. The alarm transmitter cannot send any alarms, and the alarm
center will be notified that the alarm transmitter is turned off.
DESTINATION
PRUPOSE
PORT
7190, 7195 / TCP
AddSecure alarm service
and UDP
85.117.163.240/28 corresponds to:
85.117.163.240 – 85.117.163.255
SATISFACTORY
DIODE COLOR
Yes
Green
Yes
Yellow
Yes
Red
No
Red
AddSecure Tor V, PDK-11606
12