elsner elektronik 70391 Installazione e regolazione - Pagina 11

Sfoglia online o scarica il pdf Installazione e regolazione per Unità di controllo elsner elektronik 70391. elsner elektronik 70391 18. Door operator control module

elsner elektronik 70391 Installazione e regolazione
When receiving "Output 1 + 2 - Impulse"
when object value = 1
When receiving "Output 1 + 2 - Impulse"
when object value = 0
When receiving "Output 3 - Impulse" when
object value = 0 or 1
Output 3 relay contact
Impulse mode: (1, 2 or 3 doors)
Output 1 reacts to the (is assigned to the object) Output 1 - Impulse and receives an
impulse (closes for 1 s) when the object value is 1.
Output 2 reacts to the (is assigned to the object) Output 2 - Impulse and receives an
impulse (closes for 1 s) when the object value is 1.
Output 3 reacts to the (is assigned to the object) Output 3 - Impulse and receives an
impulse (closes for 1 s) when the object value is 1.
No further settings can be made for the outputs.
Operating mode
Allows control of up to three doors
When receiving "Output 1 - Impulse" when
object value = 0
When receiving "Output 1 - Impulse" when
object value = 1
When receiving "Output 2 - Impulse" when
object value = 0
When receiving "Output 2 - Impulse" when
object value = 1
When receiving "Output 3 - Impulse" when
object value = 0
When receiving "Output 3 - Impulse" when
object value = 1
Dead-man mode: (2 doors)
Output 1 react to the object (is assigned to the object) Output 1 - Impulse. At value = 1,
the output closes; at value 0, it opens.
Output 2 react to the object (is assigned to the object) Output 2 - Impulse. At value = 1,
the output closes; at value 0, it opens.
Output 3 react to the object (is assigned to the object) Output 3 - Impulse and gets an
impulse (closes for 1 second) at object value 1.
In addition, monitoring can be set. After the monitoring period, the object is set to 0
(unless a new 1 signal is received), i.e. the output is opened:
Door operator control module KNX A3-B2 • Status: 17.12.2019 • Technical changes and errors reserved.
9
Output 1 Impulse
Output 2 Impulse
Output 3 Impulse
normally closed • normallly open
Impulse mode
nothing
Output 1 Impulse
nothing
Output 2 Impulse
nothing
Output 3 Impulse
Parameter setting