WIRING
The LSM200 must only be installed by qualified personnel. Hazardous voltage is present when generator is in
operational mode.
•
Terminal N must be connected to the neutral of the generator.
•
Electrical connections are illustrated in the wiring diagrams.
•
Choice of a proper wire size is dependent on the maximum current expected at specific terminals of the load sharing module.
Large gauge wire should be used for Current Transformer (CT) Terminals 4 to 9 as the current can reach a maximum of 5 A.
•
Long wires with high resistance can add to the burden of the CT shielded wire is recommended for sensitive control terminals, see
your specific controllers wiring diagram.