GAC LSM200 Series Podręcznik - Strona 3

Przeglądaj online lub pobierz pdf Podręcznik dla Kontroler GAC LSM200 Series. GAC LSM200 Series 11 stron. Load sharing modules

GAC LSM200 Series Podręcznik
4
WIRING
The LSM200 must only be installed by qualified personnel. Hazardous voltage is present when generator is in
operational mode.
Terminal N must be connected to the neutral of the generator.
Electrical connections are illustrated in the wiring diagrams.
Choice of a proper wire size is dependent on the maximum current expected at specific terminals of the load sharing module.
Large gauge wire should be used for Current Transformer (CT) Terminals 4 to 9 as the current can reach a maximum of 5 A.
Long wires with high resistance can add to the burden of the CT shielded wire is recommended for sensitive control terminals, see
your specific controllers wiring diagram.
lSM201 EXtRA FiltERiNG
LSM200 Series Load Sharing Modules 6-2021-B1 PIB4100
3
Governors America Corp. © 2021 Copyright All Rights Reserved