• Install a power switch or circuit breaker in the easily accessible place for supplying or
disconnecting the power.
• Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature
controller.
• When changing the input sensor, turn off the power first before changing. After
changing the input sensor, modify the value of the corresponding parameter.
• Do not overlapping communication line and power line. Use twisted pair wire for
communication line and connect ferrite bead at each end of line to reduce the effect
of external noise.
• Make a required space around the unit for radiation of heat. For accurate temperature
measurement, warm up the unit over 20 min after turning on the power.
• Make sure that power supply voltage reaches to the rated voltage within 2 sec after
supplying power.
• Do not wire to terminals which are not used.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in 'Specifications')
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website .
T N ❶ - ❷ 4 ❸ ❹ ❺ - ❻ S - ❼
❶ Size
S: DIN W 48 × H 48 mm
H: DIN W 48 × H 96 mm
L: DIN W 96 × H 96 mm
❷ Control method
No mark: Fixed control
P: Program control
❸ Alarm outputs
2: Alarm 1 / 2
4: Alarm 1 / 2 / 3 / 4
6: Alarm 1 / 2 / 3 / 4 / 5 / 6
❹ Control output 1
R: Relay
S: SSR drive
C: Current or SSR drive
Manual
For proper use of the product, refer to the manuals and be sure to follow the safety
considerations in the manuals.
Download the manuals from the Autonics website.
Software
Download the installation file and the manuals from the Autonics website.
■ DAQMaster
DAQMaster is comprehensive device management program. It is available for
parameter setting, monitoring.
Product Components
• Product
• Bracket
Sold Separately
• Communication converter: SCM Series
• Terminal protection cover
❺ Control output 2
R: Relay
S: SSR drive
C: Current or SSR drive
❻ Communication
N: None
R: RS485
❼ Option input/output
Digital
Transmission
No.
CT input
input
output
006 0
1
0
008 2
1
0
009 3
1
0
014 3
2
0
026 0
1
1
031 0
2
1
035 6
2
1
• Instruction manual
• Current transformer (CT)
• Front cover

Specifications

Power supply
100 - 240 VACᜠ, 50/60 Hz ±10%
Power consumption
≤ 8 VA
Display type
11 segment, LCD type (operating value display part: 7 segment)
Sampling period
50 / 100 / 250 ms (parameter)
Input specification
Refer to 'Input Type and Using Range'
• 0.0-50.0 A (primary current measurement range)
CT
• CT ratio: 1/1,000
• Measurement accuracy: ±5% F.S. ±1digit
Option
input
• Contact - ON: ≤ 2 kΩ, OFF: ≥ 90 kΩ
Digital
• Non contact - residual voltage ≤ 1.0 V, leakage current ≤ 0.1 mA
• Outflow current: ≈ 0.5 mA per input
Relay
250 VACᜠ 3A 1a
Control
SSR
12 VDCᜡ ±2 V, ≤ 20 mA
output
DC 0 - 20 mA or DC 4 - 20 mA (parameter), Load resistance: ≤
Current
500 Ω
Alarm
250 VACᜠ 3 A 1a
Option
DC 4 - 20 mA (load resistance: ≤ 500 Ω, output accuracy: ±0.3%
Transmission
output
F.S.)
Communication RS485
Type
ON/OFF, P, PI, PD, PID
Multi SV
≤ 4 SV
Control
Group PID
≤ 8 group
type
Zone PID
4 zones
ARW (Anti Reset
50 to 200 %
Windup)
Program
≤ 10 patterns
Program
Step
≤ 200 steps (1 pattern: ≤ 20 steps)
control
Setting type
Time setting
• Thermocouple, RTD: 1 to 100 (0.1 to 100.0) ℃/℉
Hysteresis
• Analog: 1 to 100 digit
Proportional band (P)
0.1 to 999.9 ℃ (0.1 to 999.9%)
Integral time (I)
0 to 9,999 sec
Derivative time (D)
0 to 9,999 sec
• Relay / SSRP output: 0.1 to 120.0 sec
Control cycle (T)
• Selectable current or SSR drive output: 1.0 to 120.0 sec
Manual reset
0.0 to 100.0%
Between the charging part and the case:
Dielectric strength
3,000 VACᜠ 50/60 Hz for 1 min
0.75 mm amplitude at frequency of 5 to 55 Hz (for 1 min) in each X,
Vibration
Y, Z direction for 2 hours
• OUT1/2: ≥ 5,000,000 operations
Mechanical
• AL1/2/3/4/5/6: ≥ 20,000,000 operations
Relay life
cycle
• OUT1/2: ≥ 200,000 operations
Electrical
• AL1/2/3/4/5/6: ≥ 100,000 operations
Insulation resistance
≥ 100 MΩ (500 VDCᜡ megger)
Double insulation or reinforced insulation (mark: ▱, dielectric
Insulation type
strength between the measuring input part and the power part:
3 kV)
±2 kV square shaped noise by noise simulator (pulse width: 1 ㎲)
Noise immunity
R-phase, S-phase
Memory retention
≈ 10 years (non-volatile semiconductor memory type)
Ambient temperature
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity
35 to 85%RH
Protection structure
IP65 (Front panel, IEC standards)
Loader port
• TNS: top side
Bracket
Accessory
• TNS: ≈ 128 g (≈ 156 g)
Unit weight (packaged)
• TNL: ≈ 301 g (≈ 443 g)
Approval
ᜢ ᜧ ᜣ
Communication Interface
■ RS485
Comm. protocol
Modbus RTU/ASCII, Sync-Master, PLC ladderless
Connection type
RS-485, RS-422A
Application standard
EIA RS485 compliance with
Maximum connection
32 units (address: 01 to 99)
Synchronous method
Asynchronous
Comm. Method
Two-wire half duplex
Comm. effective range
≤ 800 m
Comm. speed
≤ 115,200 bps
Response time
5 to 99 ms (default: 20 ms)
Start bit
1 bit (fixed)
Data bit
8 bit (fixed)
Parity bit
None (default), Odd, Even
Stop bit
1 bit, 2 bit (default)
EEPROM life cycle
≈ 1,000,000 operations (Erase / Write)
• 1 character of ModBus RTU is fixed at 11 bit.
• TNH, TNL: front side
• TNH: ≈ 184 g (≈ 286 g)