PACSystems RX3i CANopen Master Module User's Manual,
GFK-2831, available from
Automation-Controls/support.
Two steps are required to configure the IC695CNM001 module
as a master on a CANopen network:
Configure the CANopen network using SYCON.net and download
1.
the configuration to the CNM001 module through the USB port.
The CNM001 master module must be configured as node 1. The
slave devices are configured as nodes under the master module.
Notes:
If the Configuration command is unavailable when you right click
the node containing the CANopen Master, you must first select
Disconnect, and then select Configuration.
In the CANopen Master configuration screen, make sure the
netXDriver device driver is the only driver selected. Clear all other
driver selections.