AGS Merlin 1000Si Manuale d'uso e installazione - Pagina 7

Sfoglia online o scarica il pdf Manuale d'uso e installazione per Controllore AGS Merlin 1000Si. AGS Merlin 1000Si 9. Gas safety products, gas utility controller
Anche per AGS Merlin 1000Si: Manuale d'uso e installazione (7 pagine), Manuale di installazione e funzionamento (16 pagine), Manuale d'uso (12 pagine)

AGS Merlin 1000Si Manuale d'uso e installazione
Merlin 1000Si
Gas Utility Controller
If there are no remote emergency stop buttons installed, wire this directly to the terminal
marked [EM REMOTE].
3.6

FAN SWITCH INTERGRATION

There is the facility to connect a Fan Switch (FS1 or FS2 sold separately).
The Fan Switch provides the facility to turn the fan(s) ON when the Merlin panel is on and turn
the fans OFF when the panel is switched off
There is a dip-switch located inside the facia of the Merlin 1000Si labelled [EM SELECTION].
This is factory set in the 'OFF' position which instructs the system to shut down the fan(s) and gas
supply on activation of the Emergency shut off button(s).
On installation, this can be switched to the 'ON' position, this will instruct the system to leave
the fans on and only shut off the gas supply on activation of an Emergency shut off button.
Note: This option is not available if a Fan Switch is not installed.
3.7

AUTO-RESET

The Merlin 1000Si has a built-in auto reset feature. There is a dip-switch located on the inside
facia of the Merlin 1000Si labelled [Auto Reset].
This is factory set in the 'OFF' position, this means, if you experience a power cut, the panel has
to be restarted manually.
This can be switched to the 'ON' position and will instruct the system to restart automatically
when power is restored following a power cut or similar situation.
Rev: 04 Date: 22-10-18
User & Installation Manual
7