Typical Sensor Life Expectancy
The End-of-Life message is approximate from the first five (5) hours of continuous power!
The End of Life will depend on the type of gas your detector is targeting and may vary depending on its application
and environmental conditions such as the frequency of exposure to the target gas, poisons, or inhibitors!
The typical life of a gas detector depends on its application and intended target gas, in addition the
operational life can be prolonged if the system and equipment is installed and maintained in accordance the
instructions stated within this manual.
At the end of its predicted operational life – the detector will display an 'End of Life' screen. This message
indicates that the detector has reached its expected operational lifecycle and no gas levels are displayed.
You must contact your supplier immediately for replacement.
Sensor Type
NDIR – Non dispersing Infrared
** Normal Use. The typical life of a sensor depends on its application and intended target gas, in addition the operational
life can be prolonged if the system and equipment is installed and maintained in accordance with these instructions.
Disposing of Electrical & Electronic Equipment (WEEE)
When this product has reached the end of its life it must be treated as Waste Electrical & Electronics
Equipment (WEEE). Any WEEE marked products must not be mixed with general household waste, but kept
separate for the treatment, recovery and recycling of the materials used.
Please contact your supplier or local authority for details of recycling schemes in your area.
System Bump Test
Overview
For more help and advice on bump testing – contact us.
Always give at least five (5) minutes between testing the same unit or until gas has fully dispersed!
A bump test is a live test of the system to verify that the detector responds to gas and all connected alarm
devices, BMS, etc. are operating accordingly. It is recommended that all involved persons are informed about
the test and certain alarms might have to be inhibited (e.g., shutdown valves, notification of authorities, etc.).
If the system fails to operate as intended in an alarm state, the gas detector must not be used until a full
inspection and service has been conducted. A detector may visually appear in good working order, but its
sensitivity and accuracy can be inhibited by external factors. Dust, humidity, temperature fluctuations,
cleaning products, contaminants, exposure to its target gas or sensor drift (ageing) can cause a decline in
sensitivity, accuracy, and eventual failure.
Rev 01
Merlin Gas Detector Installation & Operation Instructions
Long Term Stability
+3% FS per annum
Lifetime**
>5 Years