ADF LINEA 100 NMV DUO Istruzioni per il supplemento - Pagina 3
Sfoglia online o scarica il pdf Istruzioni per il supplemento per Camino da interno ADF LINEA 100 NMV DUO. ADF LINEA 100 NMV DUO 17. Double sided inbuilt heater zero clearance box
ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
Dimensions for Build out (Front elevation):
• The hearth beneath the unit must include 6mm cement sheet to 1275mm x
550mm deep. The hearth in front of the unit must include 6mm cement
sheet with minimum 1240mm x 300mm deep. Total hearth size
1240x1150mm
• No combustibles within 300mm from the top of the Zero Clearance box (i.e.
to first noggin), 100mm to each side (stud).
• No combustible material to be used in construction at all in this cavity space.
• Fan cable must be below the level of the heater base and exit the cavity
below the level of the heater.
1355mm
100mm
1240mm
100mm
300mm
1/11/19
1375mm
Fig. 2
3