ADF LINEA 100 NMV DUO Supplement Instructions - Page 3

Browse online or download pdf Supplement Instructions for Indoor Fireplace ADF LINEA 100 NMV DUO. ADF LINEA 100 NMV DUO 17 pages. Double sided inbuilt heater zero clearance box

ADF LINEA 100 NMV DUO Supplement Instructions
ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
Dimensions for Build out (Front elevation):
• The hearth beneath the unit must include 6mm cement sheet to 1275mm x
550mm deep. The hearth in front of the unit must include 6mm cement
sheet with minimum 1240mm x 300mm deep. Total hearth size
1240x1150mm
• No combustibles within 300mm from the top of the Zero Clearance box (i.e.
to first noggin), 100mm to each side (stud).
• No combustible material to be used in construction at all in this cavity space.
• Fan cable must be below the level of the heater base and exit the cavity
below the level of the heater.
1355mm
100mm
1240mm
100mm
300mm
1/11/19
1375mm
Fig. 2
3